ET 5001
- 96 x 96 mm (Bezel), x 52 mm
- 1/3 Phase, 3 Element, 3/4 Wire
- 415 V LT or 110 V through PT (Line to Line)
- 5 A or 1 A through CT
- True RMS for all Power & Energy Parameters
- Supports Demand computation and captures Max Demand
- Safety: Measurement Category III, Pollution Degree 2 as per EN61010-1 First Edition
- Power Autoscaling depending on Input
- 85 – 270 V AC or DC
- Increments 1 kWH up to 866 kW and 10 kWh above 866 kW
- RS485 / BACnet Interface for external system interfacing
- Temp. 0-50 deg C, RH < 95%, non-condensing
- Accuracy: ± (0.5% of FS 0.5% of Rdg 1 digit)
± 0.2% for Frequency
± 1.0% of FS for Current